Is it possible using PRINT_CHAR to write a NULL (0x00) out M340 serial port?
Issue:
Is it possible using PRINT_CHAR to write a NULL (0x00) out M340 serial port?
Product Line:
M340, Control Expert
Resolution:
Yes, it is possible using PRINT_CHAR function block to write a NULL (0x00) out the port.
You must just define the number of character to send to include the NULL character and place the NULL character in your string
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.