All three outputs for the XMIT block are simultaneously on in 'ProWORX NxT'.

Issue
All three (3) outputs of the 'XMIT' block are simultaneously on at the same time

Product Line
'ProWORX Nxt', ProWORX 32

Environment
Windows 7

Resolution
If All three (3) outputs of the 'XMIT' block are simultaneously on at the same time, it is an indication that
the loadable was not installed correctly. The NSUP block was not loaded first.


To resolve the problem:
1.) Delete the' XMIT' block from the ladder logic for the project.
2.) Delete the 'NSUP' and 'XMIT' loadable from the project by using the following steps:

  • Click on Configuration\Configuration to open the Controller Configuration window.
  • In the 'Controller Configuration' window, click on the 'User Loadable' tab.
  • In the 'User Loadable' tab, click on the loadable block (i.e., 'XMIT') and -then click on the 'Delete' button.
  • Click on the 'OK' button to close the 'User Loadable' tab.
  • Repeat the last four (4) steps to delete the 'NSUP' loadable.


3.) If the loadable are shown in the 'Loadable Library' list, proceed to step (4). Otherwise, if it
cannot be seen in the 'Loadable Library' list, add the 'NSUP' and 'XMIT' loadable into the 'Loadable
Library' by using the following steps:
  • Click on Configuration\Configuration to open the Controller Configuration window.
  • Click on 'Loadable Library' tab.
  • Click on the 'Exe format' button.
  • Click on the 'Browse' button and browse for the loadable file (i.e., 'NSUP.exe') file.

  • Click on 'OK' to open the file.
  • Click on 'Select Library' to find and open the library.
  • Click on the 'Transfer' button to transfer the loadable into the library.
  • Click on the 'OK' button to close the 'Loadable Library' tab.
  • Repeat the last eight (8) steps to add the 'XMIT' loadable to the library.
4.) Add the 'NSUP' loadable to the project by using the following steps:
  • Click on Configuration\Configuration.
  • In the Controller Configuration window, click on 'User Loadable' tab.
  • Click on 'NSUP' in the 'Loadable Library' list.
  • Click on 'Load' to load the 'NSUP' into the project database.
  • Click on the 'OK' button to close the 'User Loadable' tab.
  • Repeat the last five (5) steps to add the 'XMIT' loadable to the project.


5.) Add the 'XMIT' block back into the project.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings