我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What could be causing a device error 513 while attempting to download firmware using DLF-3000?
Issue
While upgrading firmware for a Powerlogic meter using DLF-3000, the upgrade is unable to complete due to a Error 513.

Product Line
DLF-3000

Environment
Firmware Upgrade

Cause
This corresponds to a negative acknowledgement from the device. There is either an issue with the serial communication settings, or the ethernet connection is being used by another program.
This is causing a negative acknowledge from the target device.

Resolution
If this error occurs while connected serially, make sure the protocol mode is PowerLogic and the parity is EVEN.
Using Modbus mode or Parity of NONE will not work over a serial connection.

If this error occurs while connected over ethernet, make sure that there are no PME services communicating with the device.
With PME, stop the ION Network router service before sending firmware to the meter.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings