For the BCPM product, what is the LVCT burden (or the apparent power capacity)?

Product Line
BCPM, LVCT (Low Voltage Current Transformer)

Environment
Low Voltage Current Transformer Specifications

Resolution

The BCPM uses 1/3 V output split-core CTs for the auxiliary inputs.


The specifications for the 1/3 Volt low-voltage CTs are:

  • Accuracy: ±1% from 10% to 100% of rated current
  • Frequency Range: 50/60 Hz
  • Operating Temperature: -15°C to 60°C
  • Storage Temperature: -40°C to 70°C
  • Humidity Range: 0–95% non-condensing
  • Leads: 18 AWG, 600 Vac, UL 1015 twisted pair, 1.8 m standard length
  • Max Voltage (L-N): sensed conductor 600 Vac

The apparent power capacity (burden rating) does not apply since these are voltage-output devices, unlike traditional current-mode CTs. This is a key advantage of voltage-mode CTs (another being that they do not require shorting blocks).

Voltage-mode CTs have an internal burden resistor, typically tens of ohms or less. The meter input monitoring the CT usually has an impedance of tens of thousands of ohms in parallel with the CT’s burden resistor, which may slightly reduce the CT’s output voltage.

As long as the series resistance of the wire between the CT and the meter is less than a few hundred ohms, CT accuracy remains largely unaffected. Voltage-mode CTs can support longer wire runs using smaller gauge wire compared to traditional current-mode CTs.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings