PM870: Waveform capture misses event of interest...

Customer reports that the waveform captures evidently completely miss the triggering event such as the transition to an under-current or over-voltage condition.
Further investigation reveals that the customer has set up the waveform to be triggered by a "Standard" alarm. Standard alarms on the PM8 platform have a 1 second detection cycle (see paragraph two on page 74 of the PM8 user guide. Thus, the waveform is missing the Power Quality event of interest in the waveform captures since the 1 second update potentially results in a delay of the waveform trigger of up to 60 cycles. Instead, one must use a "Disturbance" alarm to trigger the waveform.

To do this in ION Setup software, do the following:

(1) Open the "Onboard Alarms/Events" dialog box. Here you will 4 different kinds of alarms
listed, Standard, Disturbance, Digital, and Boolean.
(2) Select "Disturbance" and click "Edit".
(3) In the "Disturbance Alarm Setup" dialog box, notice that the delay is measured in cycles
(i.e. 20 milliseconds in a 50 Hz system) as opposed to the delay measurement of seconds that is
indicated on the equivalent dialog box for Standard alarms.
(4) Configure the alarm according to your preferences and then click "OK".


Legacy KB System (APS) Data: RESL212652 V1.0, Originally authored by DaMi on 10/02/2013, Last Edited by DaMi on 10/02/2013
Related ranges: PM800 series

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings