我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
The ION7500RTU meter does not accept the .dcf meter template file via ION Setup and returns the error message: "Unable to download dcf(xml) file to a non-RMP device"

Issue

When attempting to send a .dcf meter template file to the ION7500RTU using ION Setup, the process fails and displays the error:
"Unable to download dcf(xml) file to a non-RMP device."

Product

ION7500RTU Meter

Environment

  • ION Setup software
  • ION7500RTU device

Cause

Rapid Meter Programming (RMP) is not supported on ION7500RTU meters. The .dcf file format is designed for meters that support RMP, so it cannot be applied to this device.

Resolution

Use the .fwn version of the meter template file with ION Setup instead of the .dcf file. ION Setup will treat the .fwn file similarly to how it handles .dcf files on RMP-supported meters. Refer to the attached template file for the correct format.

施耐德電機Taiwan

附件
7500-RTU_V1.1.0.fwn [311.72 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings