NAK: Target Unsupported" error message appears when attempting to upgrade an ION meter firmware with ION Setup.

Issue:

When using ION Setup to upgrade meter firmware, the upgrade fails and displays the error:
“NAK: Target Unsupported”

This error is commonly seen when attempting to upgrade the Ethernet firmware on an ION7300 series meter.


ION setup

Product Line:

ION 7300

Environment:

ION Setup

Cause:

This error can occur for the following reasons:

  • Attempting to upgrade Ethernet firmware on an ION7300 series meter while connected via serial communications.
    • Ethernet firmware upgrades on Ethernet‑capable meters must be performed over Ethernet, not over the serial port.
  • A firmware and hardware revision mismatch, such as:
    • Attempting to upgrade a revision A ION7300 meter (firmware versions 102–213) using revision B firmware (versions 250–285).
    • Attempting to upgrade a 7550 RTU meter from firmware revision 373 to revision 400.
      • These firmware versions are intended for different hardware revisions, and upgrading between them is not supported.
      • Firmware release notes describe the specific hardware differences.

Resolution:

Warning: Before downloading or installing any firmware updates, verify that the firmware iscompatible with the exact meter model and hardware revision. If unsure, contact Technical Support for guidance.

Warning:
Disconnect the device from all monitoring software before performing a firmware upgrade.

To resolve the issue:

  1. When upgrading firmware on an Ethernet‑capable ION7300 series meter, ensure the upgrade is performed using Ethernet communications, not serial.
  2. Verify that the firmware version matches the hardware revision of the meter.
    • Revision A firmware cannot be used on Revision B meters, and vice versa.
  3. Confirm compatibility using the firmware release notes before proceeding.
  4. Retry the firmware upgrade using the correct communication method and compatible firmware.

Note: ION 7300 series is currently Discontinued, for more information about replacement and others follow the link: Replacement path for old ION meters

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings