Goals and Symptoms
How to wire a 2 phase 5 wire system, on an ION 7600 Series meter
Causes and Fixes
Va1a2= 240V
Vb1b2=240V
Va1b1= 170V
Va1b2=170V
Va2b1= 170V
Va2b2=170V
Wiring and Configuration
- Use 2 PTs and 2 CTs
- VOLTS MODE = 4W-Wye
Leave V3 unconnected
________________________________________
Original article#
Date Created: July 12, 2010
Last Revised: July 20, 2010
Public
Original Author: SN
All content © 1992-2010 Schneider Electric
Legacy KB System (APS) Data: RESL202963 V1.0, Originally authored by LaAd on 07/21/2010, Last Edited by LaAd on 07/21/2010
Related ranges: ION7500/ION7600
發佈於:施耐德電機Taiwan

