How to configure Read_var instruction to read 4x registers from Modbus server using Unity Premium Processor.

Goals and Symptoms

This resolution is intended to be used as a guide to demonstrate how to configure the read_var instruction to read 4x (%MW) registers from Modbus server over a RS485 Network.

Facts and Changes

This example uses a TSXSCP114 RS485 communication card installed in channel 1 of the TSXP57104 processor. The Modbus server is a TSX Micro PLC with the TER port configured for Modbus server address 1.

Hardware

hardware
TSXP57104M Unity Processor
TSXSCP114 PCMCIA communication card.
TSXPACC01 RS485 Tap Link box
TSX372100 Micro PLC (Modbus Server device)

Operation and Debug

1, Create an animation table, enter the variables below. Click the Modification button. select the value for %M1. Click the up arrow to force the vale high.
This will initiate the Read_var instruction. Turn the block off with the down arrow.

table

Debugging

Management parameters:
%MW 10 - contains the Exchange number. This will change to an even number upon completion.
%MW11 - Should be viewed in Hex High byte - Operation Report, Low Byte - Communication Report
%MW12 - Time Out in 100ms
%MW13 - Length of data received

When on-line with the controller it is possible to see all slave devices connected to the Channel from the debug screen.
controller

Upon each operation the COM LED will flash on the TSXSCP114 card.
The TER LED will also Flash on TSX Micro each time it is polled.

Attachments

The zip file below contains both Unity and PL7 programs.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings