Setting up a Write_Var command to have a M340 PLC write data directly to a supported TCP/IP device.

Follow the below procedure :

  1. Create an Ethernet I/O network — In your Unity Pro project, add a new Ethernet network, configure it for your application, and validate the changes.
  2. Link the network to the CPU's Ethernet port — In the hardware configuration, assign the network you just created to the CPU's built-in Ethernet port.
  3. Enable array entry in project settings — Go to Tools > Project Settings and check the data-type options that allow arrays to be entered directly, instead of having to declare them as variables first.project option
  4. Add an ADDM block — Set its IN parameter to the target device's IP address as a quoted string, in the form 'TCP_IP{x.x.x.x}' — quotation marks required on both sides since it's a character string.
  5. Add and wire a WRITE_VAR block — Connect the ADDM block's output to a WRITE_VAR (or READ_VAR) block to complete the data exchange with the target device.


Below an example with the NetLink id "Ethernet_1" and IP address of the device 192.168.40.11.
Next configure the remaining parameters of the Write_Var block where:

OBJ = String declaring the type of object to Write (%MW or %M)
NUM = The starting register address in the Slave device to were the data will be sent
NB = The # of registers to write
GEST = Array of length 4 where the Management Exchange table for the Write_Var is located
EMIS = Array of length NB where the Write data is stored in the M340.
Note: The Array's are of type INT if declared as variables.

WRITE_VAR , example


Finally build, download, and run the program

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings