我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to perform a soft reset on a CM3000/4000 and PM800 series

Issue
Unable to power cycle the meter physically.

Product Line
CM3000/4000

PM800 series

Environment

PM800 Series and CM3000/4000 Series

Modbus Tester or other Register Writing Applications

Causes
Sometimes local access to where the meters are installed isn't possible or access to the wiring of the meter is blocked.

Resolution

Can remotely perform a soft reset of these devices by writing a specific register value to the setup register.

Will require an application or tool like Modbus Tester or some other software that allows the user to write to the registers of the devices.

  1. Write 9020 to register 8000 to put the device in setup mode.
  2. Write 1110 to register 8000. This will reset the meter.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings