我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How to add a ModemGate site to ION Setup

Issue
A ModemGate site needs to be added as a new site in ION Setup to facilitate communication with modem connected devices.

Product Line
ION Setup 3.0,3.2

Environment
ION Setup

Resolution
1. Open ION Setup in Power User Mode (leave "Single ION device configuration mode" unchecked).
- Right-click>>Insert Item...>>Site and click OK to add a new site
- Choose the Comm Link as Modem and enter the phone number, then click the "Modem configuration..." button
- Select the port settings, then click the "Modem Profile" button to access the Modem Profile Selection Wizard. This will guide you through a series of configuration screens to set up your local and remote modem

IOn Setup configuration screens

2. Add each device on the serial loop to the ModemGate site you created.
- Right click the new site you added and select Insert Item...
- Select Device and click OK.
- Configure the new device, and then click OK.

The Network Viewer should resemble the image below:

ION Setup Network view

ModemGate Checklist:
- Confirm that the gateway meter's phone number is correct
- Confirm that the gateway meter's appropriate COM port is used for the gateway and ensure the protocol is set to ModemGate
- Confirm the baud rate and unit ID settings for each serial device

The video below depicts how to configure a ModemGate site using the ION Setup software.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings