Why does Unity Pro Configuration of the rack shows a red slot number for the Quantum 140CPS11420 power supply?

Title

Why does Unity Pro configuration of the rack shows a red slot number for the Quantum 140CPS11420 power supply?

Issue

Product Line

Unity Pro, Quantum

Environment

Cause

Resolution

That means that Unity is not seeing the correct module ID in that slot.  If you have selected 140CPS11420, try selecting 140CPS114X0 (or vice versa) and the red slot number will go away.