我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How can you program the R1 or R2 relays on the ATV31 or ATV312 drives?

Issue:
Programming the R1 or R2 on the ATV31/ATV312 drives.

Product Line:
ATV31 or ATV312

Environment:
All

Cause:
Setting up R1 and R2 relays on the ATV31 or ATV312 drives?

Resolution:
Note: "press Enter" means press in on the dial, and "scroll down" means turn the dial clockwise.

  1. While at RDY on the drive's display, press Enter
  2. Scroll down to I/O menu and press Enter
  3. Scroll down to R1, press enter, and choose your desired setting. Example: FLT is drive fault.
  4. Scroll down to R2 enter and choose your desired setting. Example: RUN is drive running.


For further detail, please refer to page 50 in the ATV312 Programming Manual.
https://www.se.com/ww/en/download/document/BBV46385/

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings