我们今天能为您提供什么帮助?

Why might an ATV212 Drive always run at the low speed setting and not follow the analog input signal?

Issue:
ATV212 running at low speed and not following the analog input signal

Product Line:
Altivar ATV212

Environment:
All

Cause:
Drive is not following the remote analog signal coming in on VIA or VIB

Resolution:
The low speed setting is parameter LL.

Verify that the VFD is setup to look for the analog input:
DIP switch SW100 position VIA at U (voltage) or I (current), VIB at U (voltage)
Frequency mode select, FMOd:
1 = VIA input
2 = VIB input

Verify the analog input signal by measuring the mA or Vdc on VIA / VIB.  Also check polarity, (+) on VIA / VIB and (- ) on CC.

Logic input R has factory default assignment as preset speed, F112 = 6, Sr1 = 15Hz.  If R is active, the VFD will run at 15Hz or LL (low limit) only. Check / correct the R input status and assignment.  Note that in an S-Flex product, R is a run permissive input, F112 = 1.  If a replacement ATV212 is installed or the VFD was reset to factory defaults, reprogram the VFD per the S-Flex manual.

Verify that the PID parameter, F360, is set correctly:
0 = no PID control
1 = PID per VIA feedback
2 = PID per VIB feedback

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings