Object Error in ENM
Issue
In ENM while selecting Email from the Relay Name drop down list, an object error message opened:



Product Line
Event Notification Module 7 (ENM)

Environment
Web Browser
Internet Explorer
Windows Server 2008 R2

Cause
Windows updates were applied and IE8 (Internet Explorer 8)  was upgraded to IE11.
ENM 7 only supports IE8 in compatibility mode.

Resolution
Internet Explorer 11 was uninstalled and the browser went to the default IE8.  This resolved the problem.