How to setup a PTC alarm without tripping the ATV61 drive?

Article available in these languages: 西班牙文

Issue:
PTC alarm installation

Product Line:
Altivar 61, Altivar 71

Environment:
All models, all serial numbers

Cause:
Using PTC probes for motor overload protection, requesting warning indication rather than faulting the VFD

Resolution:
PTC warning can be indicated via a relay output assigned to an Alarm Group.
Example for SW2 switch set to PTC, PTC connected to LI6, R2 indication, Alarm Group 1

1.8 Fault Management
PTC Management - activates the PTC monitoring
LI6 = PTC Probe [PTCL] = Always

Motor Thermal Prot - Inactivates the VFD internal I2T overload protection
Overload Fault Mgt [OLL] = Ignore

1.5 Inputs/Outputs CFG
R2 Configuration - assign relay R2
R2 Assignment [R2] = Alarm Grp1

Alarm Grp1 Definition - activate PTC alarm for the warning group
LI6 = PTC Alarm [PLA] = ON

Important note:  When Overload Fault Mgt [OLL] = Ignore, the motor thermal protection by calculating the I2t is inactive.  The drive will not provide motor overload protection based on motor current.  Both functions can work at the same time by keeping Overload Fault Mgt [OLL] = Freewheel

施耐德電機Taiwan

附件
atv61_programming_manual_en_1760649_08.pdf [4.35 MB]
探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings