我们今天能为您提供什么帮助?

How can I see the last faults that occurred on an ATV61 or ATV71 drive?

Issue:
ATV61/ATV71 last faults

Product Line:
ALTIVAR 71 ATV71 ATV61 Altivar 61

Environment:
All

Cause:
Faults

Resolution:
Go to menu 1.10 Diagnostics then to Fault History.
Faults are listed most recent to oldest.
You can highlight and press enter on each fault to confirm a number of things that registered at the time of fault.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)“

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings