Can the ATV312 Drive switch from local keypad control to remote terminal control by pressing and holding the mode button?
Issue:
ATV312, local mode to remote mode.

Product:
ATV312  Altivar 312

Environment:
All

Cause:
Programming was changed.

Resolution:
The drive can be changed from remote (Terminal) mode to local (Keypad) mode by pressing and holding the mode for 3 seconds.
However, when returning to remote from local requires the drive to be reset to factory defaults using the FCS parameter in the drC menu.
Consult the ATV312 Programming manual for details.
https://www.se.com/ww/en/download/document/BBV46385/