How can you put the ATV61 and ATV71 drives in a NET command control mode?
Issue:
ATV61 and ATV71 drives controlled in a NET command control mode.
Product Line:
Altivar ATV61 and ATV71 with an Serial communications option card.
Environment:
All
Cause:
The drive is showing Terminal control mode they need to set it up for NET control.
Resolution:
Basic Programming settings will be
Set up your communications card in menu 1.9
In Menu 1.6:
-Set your Ref 1 1 channel to com card
-Set your Profile to be not separate
or
Set your Profile to be Separate then CMD switching to a logic input or choose channel reference as com card.
Attached is the ATV61 Programming Manual to assist if needed.
ATV61 and ATV71 drives controlled in a NET command control mode.
Product Line:
Altivar ATV61 and ATV71 with an Serial communications option card.
Environment:
All
Cause:
The drive is showing Terminal control mode they need to set it up for NET control.
Resolution:
Basic Programming settings will be
Set up your communications card in menu 1.9
In Menu 1.6:
-Set your Ref 1 1 channel to com card
-Set your Profile to be not separate
or
Set your Profile to be Separate then CMD switching to a logic input or choose channel reference as com card.
Attached is the ATV61 Programming Manual to assist if needed.
發佈於: 施耐德電機Taiwan