Should the drive or softstarter be disconnected prior to meggering the motor or motor wires?
Issue:
Drive or softstarter recommendation prior to meggering the motor or motor wires
Product Line:
All variable frequency drives and soft starts
Environment:
All models and serial numbers
Cause:
Meggering the motor
Resolution:
Yes, the drive or soft start must be disconnected before a megger test is performed on the motor or motor wires.
Drive or softstarter recommendation prior to meggering the motor or motor wires
Product Line:
All variable frequency drives and soft starts
Environment:
All models and serial numbers
Cause:
Meggering the motor
Resolution:
Yes, the drive or soft start must be disconnected before a megger test is performed on the motor or motor wires.