我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to Change the Option Module Communication Issue Reset Behavior in the PM8000/ION7400/ION9000 series?
Issue
How to change the default behavior of the PM8000/ION7400/ION9000 options module bus to not automatically reset on an error.

Product
PM8000 series
ION7400 series
ION9000 series

Environment
ION Setup

Resolution
The default behavior is to reset the bus automatically on an error. The steps below can be used to change this behavior.

NOTE: Changing this behavior will require a user to manually reset the bus when a communication error occurs.

The reset can be performed via the front panel, web pages or by pulsing the option module reset the external Boolean module.
  1. Connect to the meter using ION Setup. *
  2. Set the meter to advanced configuration mode. *
  3. Open the Factory Module folder and open the FAC1 module.
  4. Change the Opt Mod ResetBusOnError setup register from Automatic to manual.
Screenshot of the Setup register
  1. Send changes to the meter and disconnect from ION Setup.

* Refer to the ION Setup User guide for more information 7EN02-0312-00


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings