我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Will an Altivar drive run with Output phase loss set to YES and single phase input to the drive?
Issue:
Is it possible to run an ATV312 drive with Output phase loss set to YES and with a single phase input to the drive?

Product Line:
All single-phase input ATV312 drives

Environment:
ATV312 drives

Cause:
Detection is looking for ripple voltage only

Resolution: Per Level 3 Tech Support in France:
This is how the ATV312 drive detects a Mains Input Phase Loss.  This detection is only done by software, by measuring the ripple voltages on the DC bus.  For this size of drive, if the ripple is over 26V, a fault occurs.  That means that if there is no load on your motor, there is no bus ripple on the DC bus and of course there is no fault.

The PHF fault is only present on the ATV312's to protect the ripple on the capacitors, to avoid an explosion.

There is no hardware detection, which is the  same as in ATV71, to detect if the main wires are present or not. This detection needs additional hardware components and will raise the price of the product.  But your drive can run safety, protected by this function.

Another case where the detection is not so much operational, when your drive runs with small motor.

In this case, even with heavy load there is no ripple voltage on your DC bus, because the capacitors are so big, you will detect an input phase loss.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings