As per catalog GV2ME - Ambient temperature shown as "Operation - Open mounted -> -20 ... +60 °C & Operation - In Enclosure -> -20 ... +40 °C". Do we have to de-rate for +50 in enclosure?

Our GV2 and GV3 thermal-magnetic circuit breakers have a temperature compensation system.
This system allows retaining the thermal tripping level when the ambient temperature is from -20° to 60°C for the open offer and from -20°C to +40 °C for the enclosed offer.

For a GV2 or GV3 installed as an “open” device, meaning mounted in a larger industrial control panel along with other devices, they are rated for 60 °C.  This means the ambient air around the device can be up to 60 °C.  They can be installed at an ambient temperature of up to 70 °C if derated by 1% for each 1 °C increment above 60 °C.

For an enclosed GV2 or GV3, meaning purchased already mounted within the enclosure and intended to be the only device within that enclosure they are rated for 40 °C.  This ambient refers to the temperature outside of the enclosure.  These can be installed in an ambient temperature of up to 50 °C if derated by 1% for each 1 °C increment above 40 °C.

In either case, you can not exceed a temperature above 70°C for open-mounted and 50 °C for enclosure mounted.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings