Video: How is the automatic restart function enabled on Altivar Process drives?

Resolution:

To activate this feature, follow these steps on the drive:

  1. Set the control mode

    • Go to: Complete Settings → Command and Reference
    • Set 2 wire type to Level Control
  2. Enable automatic restart

    • Go to: Complete Settings → Error/Warning Handling
    • Set Auto Fault Reset to Yes
  3. Retry duration

    • The drive will attempt to reset the fault during the time defined in Fault Reset Time
    • Default value: 5 minutes

For automatic restart to work properly, all of the following must be met:

  • The drive must be configured in 2-wire control mode
  • A run command (RUN) must be active
  • The fault must be resettable automatically
  • The cause of the fault must be resolved

Note: This function does not work if the drive is controlled via the HMI or serial communication.

Enable Catch on the Fly (under Error/Warning Handling) so the drive can synchronize with the motor if it is already spinning when the restart occurs.

The lists of fault codes that can be cleared automatically are listed in the ATV600 Programming Manual and ATV900 Programming Manual.


Si este artículo no responde a tu pregunta, consulta nuestra base de datos de preguntas frecuentes, donde encontrarás respuestas a las preguntas más comunes:
Preguntas Frecuentes - Schneider Electric (se.com)

Si la sección de preguntas frecuentes no resolvió tu problema, puedes llamarnos al  55 5804 5000 Opción 1, Opción 2 o enviarnos un correo electrónico a customercare.mx@se.com para crear un caso con nuestro equipo de Soporte Técnico.

Si no te encuentras en México o Centroamérica, por favor contacta a tu Centro de Atención al Cliente local para recibir asistencia:
Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。