我们今天能为您提供什么帮助?

Cannot download to new or replacement HMIGTO. "Incompatible version of Runtime" error appears

Article available in these languages:

  • 西班牙文

Issue:
Unable to download to a HMIGTO HMI. Error is "Incompatible version of Runtime".

Product Line:
HMI, Magelis

Cause:
You may have a HMI unit that is no longer supported by your version of Vijeo Designer.  This occurred when Schneider Electric increased the DRAM memory of the HMIGTO to support Vijeo XD.  The chips were upgraded to 256 MB (128 MB usable for Vijeo Designer).

Resolution:
Check the date of manufacturing sticker on the HMI unit.  If it starts with 16 or greater, then this is the newer design with increased memory.
Check your version of Vijeo Designer.  It needs to be version V6.2 SP4.1 or higher.
If you have an older version of Vijeo Designer you must update it.
Schneider Electric's software download center can be accessed at https://www.schneider-electric.us/en/download/

NOTE: If your issue persists, please reach out to us at Technical Support:
https://www.se.com/us/en/work/support/customer-care/brand-selection/

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings