Can the Altivar drive's freewheel stop function, be use with a normally open contact ?
Issue:
Altivar drive's freewheel stop function assigned for make or break activation.
Product Line:
Altivar
Environment:
ATV61 ATV71 ATV312 ATV12, ATV32
Cause:
Normally open contact close to freewheel
Resolution:
No option in the drive settings to reverse the freewheel logic function.
Assigned logic input, must be active +24vdc (made) break to trip.
Altivar drive's freewheel stop function assigned for make or break activation.
Product Line:
Altivar
Environment:
ATV61 ATV71 ATV312 ATV12, ATV32
Cause:
Normally open contact close to freewheel
Resolution:
No option in the drive settings to reverse the freewheel logic function.
Assigned logic input, must be active +24vdc (made) break to trip.