我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Declaration of conformity to Machine directive (EN 13850) for shrouds (E-Stop protection)

Article available in these languages: 法文

There is no declaration of conformity regarding the Machine Directive for accessories. The conformity depends of the way it is used by the machine manufacturer (in this case, type of E-Stop used)
You can find certificate of conformity for E-stop in Shopping kiosk
Even if the shroud ZBZ160* is used with appropriate E-Stop operators, some safety organisms could argue that this accessory could hamper a free use of the E-stop (one's hand can hit the guard if the E-stop is strongly activated) in reference to the § 4.3.1 of the EN 13850 ed 10-2015 ("4.3.1 Emergency stop devices shall be designed to be easily identified and actuated by the operator and others who could need to actuate them. The actuator of the emergency stop device may be one of the following types:
a) pushbuttons easily activated by the palm of a hand").
The best, regarding the Machine Directive, would be to separate the functions : Emergency stop and electrical lockout
The telescopic shroud (ZBZ3605) reduce the risk of questioning. See certificate for ZBZ3605 shroud in attachment

施耐德電機Taiwan

附件
17-001 C&S XBZ3605 Conformity to EN 13850.pdf [15.73 KB]
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings