我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Can I configure the ATV312 drives to shut down immediately if the motor current exceeds a limit that I can define?

ISSUE:
How do I configure the ATV312 to shut down immediately if the motor current exceeds a limit?

PRODUCT LINE:
ATV312 series drive

ENVIRONMENT:
All models, All serial numbers

CAUSE:
Dedicated function not present in ATV312 series drives.

RESOLUTION:
This is possible if the Analog Output of the drive is not being used and you have an unused logic input.

Under the I-O menu, set Parameter DO to function CTA (Current Threshold Attained) : This function uses the AOV terminal as a logic output instead of analog output and defines that the output will be high whenever the motor draws more current than the given set point.

Under the SET menu, set parameter CTD to the desired amount of motor current. If your motor current exceeds this point, AOV output will go high.

Under the FLT menu, set parameter ETF to LIX where X = an unused logic input on the drive. : This assigns an External Fault function to a logic input.

Under the FLT menu, set parameter LET to High : This causes the external fault function to be triggered when LIX (from previous step) is at logic high condition.

Install a jumper wire between AOV and LIX : This ties the logic output to the external fault input.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings