我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
The Model 6 Motor Control Center motor starter unit was started and it would not hold in what should I do? Common startup issues for motor starter units with Tesys T overloads
Scenario: All the terminations are complete and when the motor was started the starter would not "hold in". In this scenario, if the starter does not "hold in" meaning that the Over Current Protective Device (OCPD) trips or the Starter Overload Trips, try the following steps for resolution.
The attached document (M6MCC-Starters-Tesys T-TroubleShooting-Guide-V2_1) will help guide you through the steps to ensure proper settings for the OCPD and the Tesys T overload have been set. Use of this document may save time prior to contacting Schneider Electric Square D for assistance.
NOTE: Prior to performing any changes in the equipment settings, ensure all electrical safety precautions and electrical safe work practices are followed. Schneider Electric always promotes working on de-energized equipment whenever possible.

施耐德電機Taiwan

附件
M6MCC-Starters-TesysT-TroubleShooting-Guide-V2_1.pdf [527 KB]
探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings