我们今天能为您提供什么帮助?

Why does an Altivar drive HMI display flash or blink during run state?

Article available in these languages:

Issue:
Altivar Drive HMI blinking during run status.

Product Line:
ATV12  ATV312  ATV32  ATV320

Environment:
All models

Cause:
HMI is flashing

Resolution:
A flashing HMI display indicates that the current limitation is being exceeded.
Verify the drive settings for nCr, nSP, UnS and CLI
Monitor motor current when the drive is running, for overcurrent condition.

施耐德電機Taiwan

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。