How to do program the ATV630 for 2- wire control and where do I connect the start / stop?
Issue:
Program the ATV630 for 2-wire control and connect the start / stop.
Product Line:
ALTIVAR 630
Environment:
All serial numbers
Cause:
Installation / Setup
Resolution:
Go to menu 5 Complete Settings
Go to menu 5.5 Command and Reference
Set 2/3 wire type to 2 wire .
24V to DI1 = forward (normally open , maintained close to start)
Program the ATV630 for 2-wire control and connect the start / stop.
Product Line:
ALTIVAR 630
Environment:
All serial numbers
Cause:
Installation / Setup
Resolution:
Go to menu 5 Complete Settings
Go to menu 5.5 Command and Reference
Set 2/3 wire type to 2 wire .
24V to DI1 = forward (normally open , maintained close to start)