Video: How to modify the energy accumulation values on an ION meter
Issue
It may be required to set the energy readings of an ION meter to specific value. An example of this is when a meter swap out occurs, and the user wants to start the energy accumulation from the previous meter's readings.

Product Line
ION86xx series meters
ION76xx series meters
ION75xx series meters
PM8000 series meters

Environment
ION Setup

Resolution
ION Setup can be utilized with 'ION framework' meters to modify energy values.
For the ION setup download and documentation, please reference FA212816.


1. Within ION Setup, connect to the desired meter and open the Setup Assistant.
2. Select Template in the left hand pane of the Setup Assistant.
3. Select the Register Edit tab.
4. Under Register Edit, highlight Energy. With Energy selected, click the Display button.

Video: How to modify the energy accumulation values on an ION meter

5. The Register Editor window will appear. Click Edit.

Video: How to modify the energy accumulation values on an ION meter

6. Enter the meter password and click OK. It is now possible to modify the Energy values.

Video: How to modify the energy accumulation values on an ION meter

8. Once the desired values have been input, click 'Send'. (Ensure that the corresponding box is checked for each field that was modified.)

Video: How to modify the energy accumulation values on an ION meter

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings