我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What is the process to cycle input power to a variable frequency drive in order to reboot it?
Issue:
Drive has detected a fault that requires a reboot of the drive to clear

Product Line:
All Altivar products.

Environment:
All

Cause:
Reboot needed to clear latched fault code.

Resolution:
To properly reboot an Altivar VFD, disconnect three phase input power from the L1, L2, L3 terminals. Observe the main display of the drive, it will remain lit for some time after power is removed to the drive, between a few seconds to a few minutes depending on the horsepower of the drive. Once the main display shuts off, wait another 5-10 seconds before reapplying power to the drive. Failure to allow sufficient time before reapplying power to the drive can cause the fault code to remain latched in the drive.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings