Issue:
Possible causes for ULF Underload Fault on ATV212 Drive.
Product Line:
Altivar ATV12
Environment:
All
Cause:
Programming
Resolution:
Under [ConF] > [FULL] > [I_0-] > [ULt] Underload monitoring was set to 3s. If you do not want that monitored set back to 0s.
Possible causes for ULF Underload Fault on ATV212 Drive.
Product Line:
Altivar ATV12
Environment:
All
Cause:
Programming
Resolution:
Under [ConF] > [FULL] > [I_0-] > [ULt] Underload monitoring was set to 3s. If you do not want that monitored set back to 0s.
發佈於:施耐德電機Taiwan

