Importing a configuration file that was created using another BMXNOR0200 could fail if the size of the file too large.

Issue
Importing a configuration file that was created using another BMXNOR0200 could fail if the size of the file too large.

Product Line
BMXNOR0200

Environment
Windows 7, windows 8, Windows 10. All versions of exec firmware for the BMXNOR0200.

Resolution
When a configuration file is imported into the BMXNOR0200, it will consume memory within the module.  If the file size exceeds the amount of free
memory available in the BMXNOR0200, the import will fail.  This could occur if the file was created by exporting it from another BMXNOR0200 module
that contained a huge amount of variables defined in the DNP3 'Data Mapping' web pages.  When the configuration is exported from a BMXNOR0200 in this
situation, it will creates a file that could be larger than the actual memory size within the BMXNOR0200 module.  During the creation of the export file on the PC,
the operation extracts the information from the BMXNOR0200 module and writes it to an ASCII text file.  The export of the file will not have any problems
exporting because there is sufficient free memory on the PC.

When the file is imported in to the BMXNOR0200 module, the following occurs: (This action also consumes memory.)
  • The file is downloaded to the web server within the BMXNOR0200.
  • The module performs a check of the imported information.
  • The information is parsed from the file to the respective locations within the module.

It is recommended to check the free memory available within the BMXNOR0200 module and compare it against the file size.  this can be performed by:
  • Click on 'Memory' in the BMXNOR0200 web page to open the 'Memory Diagnostics' web page.
  • Compare the 'Free Memory Size' against the file size.

To resolve the issue, the following workaround is recommended:
  • Use an array data type. rather than configure each point one by one.  The 'Array' type is more efficient.
  • If a variable name is required for each point, an alias can be used on array.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings