Which modular batteries can be used with the Galaxy VS All in One (AIO) model?

Article available in these languages: 西班牙文

Issue:
Which modular batteries can be used in the Galaxy VS All in One (AIO) model?

There are 7 Ah and 9 Ah batteries. Can they be mixed?


Product line:
Galaxy VS All in One


Environment:
All models, all serial numbers


Cause:
Galaxy VS AIO model has the option to work with modular batteries.  The modular batteries are available for installation in the main frame as well as external battery frames for extended run time.  Modular battery options are 7 Ah and 9 Ah batteries.  This has raised questions on installation and operation.

Wide Frame UPS, Tall Frame UPS, and Modular Battery Cabinet:
7 Ah batteries - Not Validated. UPS will stay in constant battery fault alarm.
9 Ah batteries – Accepted and Approved

Narrow Frame UPS:
7 Ah batteries – Accepted and Approved
9 Ah batteries – Not Validated. UPS will stay in constant battery fault alarm.

Mixed Batteries in any system:
Forbidden.  UPS will stay in constant alarm.

The different types of batteries require different charging rates, current limits, and charging curves.  It is not possible to program different batteries into a UPS.

Battery Part Numbers:
GVSBTU        Galaxy VS 7 Ah Smart Modular Battery (single module)
GVSBT4         Galaxy VS 7 Ah Smart Modular Battery String (4 modules)
GVSBTHU     Galaxy VS 9 Ah Smart High Capacity Battery (single module)
GVSBTH4      Galaxy VS 9 Ah Smart High Capacity Battery String (4 modules)


Resolution:
Install the proper rated batteries into the UPS.  Confirm battery types are not mixed.


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings