我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to setup Debug Diagnostic to get dump files for PSO troubleshooting
Issue
How to extract dump files from PSO processes. This is useful when an exception has occurred.

Product Line
Debug Diagnostic

Environment
PowerSCADA Operation (PSO)

Cause
The Debug Diagnostic Tool (DebugDiag) is designed to assist in troubleshooting issues such as hangs, slow performance, memory leaks or memory fragmentation, and crashes in any user-mode process.

Resolution
While the attached document outlines the procedure with screenshots, below are the steps:
  1. Download debug diagnostics from: https://www.microsoft.com/en-us/download/details.aspx?id=58210

  • Start up the “DebugDiag 2 Collection” application and press “Cancel” on the “Select Rule Type” popup.

  • Switch to the “Processes” tab

  • Select the “CitectIDE.exe” process, right click and select “Create Full Userdump”

  • Select the “CtDraw32.exe” process, right click and select “Create Full Userdump”

  • Collect the two dumps from the specified location and send them to support!

施耐德電機Taiwan

附件
DebugDiagnostic.pdf [432.95 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings