Can I Use PowerTag NSX on a TN-C Grounding System ?
There is no restriction to connect the External Neutral Voltage Sensor of a PowerTag NSX (white wire) to the PEN of a TN-C Grounding System.

This kind of connection will not have any impact on the :
  • measurement precision of the PowerTag NSX
  • protection feature of the Compact NSX Breaker