How to Update the Application for the Vigilohm IMDLRDH
Note: Implementing a new application in your IMDLRDH will erase your previous configuration.
To update the application program of your IMDLRDH you need to:
Have a formatted USB Pen Drive in FAT32 format.
Unzip the content of application zip file and place the extracted files on the root of your USB Key.
Switch off the IMDLRDH
Plug the USB Key in the USB port of the IMDLRDH
Power on the IMDLRDH, wait until the installation confirmation screen appears.
Press Yes to Start the installation.
Device will restart and installation will start automatically.
Wait for the program to be installed completely in the IMDLRDH
Once installation is complete this screen will appear.
Remove the USB Pen Drive and click restart.
After these steps you need to perform the commissioning of your IMDLRDH.