我们今天能为您提供什么帮助?

Can the Connexium log file be used to troubleshoot network issue.

TCSESM Connexium Switch logs usually do not provide enough information to troubleshoot an issue.  Typically, assistance from Belden or a Google search the message shown in the log can help understand it's meaning.  However, there is not enough information in the logs to help troubleshoot an issue with a Ethernet module.

We normally rely on the network topology diagram and Wireshark traces of the Ethernet traffic going to and from the Ethernet port on the module. Usually, we request a Wireshark trace of the Ethernet traffic before, during and after the issue occurs. The trace should be taken in promiscuous mode using either a hub or mirrored port on a managed switch.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings