Masterpact MTZ: Components needed to locally operate breaker via smartphone app

Issue: Local operation via phone app capability was not ordered from the factory.  Need to field modify.
Product Line: Circuit Breakers
Environment: Masterpact MTZ

Resolution: to field modify, the following components are required. Some of these parts may already be installed.

  • Mobile App – EcoStruxure Power Device
  • Masterpact Operation Assistant Digital Module LV850005
  • XF-Com, MX-Com coils, part numbers vary based on voltage.
  • Spring Charging Motor, part numbers vary based on voltage.
  • Isolation Module LV850056SP

Isolation module

  • Isolation Module to coils communication cables MTZ1: LV833118SP, MTZ2/MTZ3: LV847904SP

isolation module to coil cables

  • MX-Com cable needs to be plugged into the MX1 location on Isolation module, not MX2.

Isolation module MX1 wiring location

  • Coils properly wired, C3 and A3 continuously powered. C2 and A2 are only needed for push button operation.

coil wiring diagram

  • Accessories Declared in the Control Unit via EPC, click the accessory pencil

edit breaker accessories


Then declare accessories
declare accessories

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings