"Configured" status is not displayed in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
Issue
"Configured" status is not displayed (checked or unchecked)  in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
image.png
Product Line
PO2021 PSO2020 R2 CU1
Environment
PO2021 / PSO2020R2CU1 with webHMI application having SMD devices
Solution
  1. Close any open webHMI application in browser
  2. Stop IIS from IIS Manager
  3. Navigate to C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  4. Take backup of "Thermal" Folder in v2021 folder and its sub-folders (C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021)
  5. Replace the attached (Related) TGML files in Thermal folder normally located at C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  6. If your installation location is different, please make sure you replace these files in Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  7. Start IIS Manager
  8. Open the TGML for SMD and verify the "Configured" Status visible for all Cubicles.
  9. If not able to view updated TGMLs , perform iisreset using Command Prompt (Required Administrator privileges).

施耐德電機Taiwan

附件
Thermal tgml files.zip [759.01 KB]
探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings