我们今天能为您提供什么帮助?

What are the limitations of Unity Pro Dif V14SP2?

Issue:
Limitations of Unity Dif V14SP2

Product Line:
Unity Pro, EcoStruxure Control Expert, Unity Dif

Resolution:
-  Comparison in Offline mode only
- Unity DIF will compare offline project files from the same PC or from remote PC . In this mode, it’s not possible to compare a project file directly with a project embedded into a PLC

- Use of Security Editor
a.  If the Security is ON in UnityPro or EcoStruxure Control Expert, Unity DIF will compare project files after asking for the appropriate profile to be used. However, for Unity DIF to function correctly, the profile should have rights to at least do the following: Open an existing project, Import and Save project. In case of default UnityPro or EcoStruxure Control Expert profile, it is recommended to use the PROGRAM profile.
b.  If the Security is ON in UnityPro or EcoStruxure Control Expert, the samples cannot be used directly. Need to modify them to provide the username and password of the correct profile to be used for the comparison and recompile the samples.
c.  If the Security is ON in UnityPro or EcoStruxure Control Expert with no login or avoidable login, Unity DIF will still prompt for the username and password. Provide the username and password of the correct profile to be used for the comparison

-  Project Settings Limitation
Since few Project Settings have been changed from UnityPro or EcoStruxure Control Expert 14.0 onwards, the comparison of project files of earlier versions may contains added or deleted differences in the Project Settings section.

-  Removal of whitespaces during Project Import / Export in UnityPro or EcoStruxure Control Expert
During project Import / Export in UnityPro or EcoStruxure Control Expert, it could happen that whitespaces at the beginning or at the end of certain language elements are being removed which leads to insignificant differences displayed in Unity DIF.

-  SFC Program Comparision under POU.
SFC program comparision is not supported under POU section.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings