Why am I unable to set "LAR" to DI4 with SoMove when using Master/Slave on a Process Drive?
Limit Switch function LAF and LAR can only be assigned a digital input whenMaster/Slave MSID and MSDT are both set to Master.If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)