MiCOM P12x/y – Latest fault record extraction over Modbus

Issue
We have MiCOM P123 protection relays and found a issue in fault record extraction over Modbus.

If accessed via Modbus RTU RS485, the relay server houses this data in 25 contiguous addresses 3700h-3718h. in this case, the data structure used is a circular list, where the most recent fault is stored in the +1 address of the last one inserted, that is, as if it were a queue. Therefore, the last fault will have a variable memory address. This forces us –in principle- to bring all the faults to be able to analyze them and locate the last one, which will finally be the one we will keep, discarding the others.

If accessed via the keypad on the front of the relay, the last fault –or most recent- is always in the same position, as if it were a battery. This will always be at the top of the stack, and you only have to access it to locate it. As you go down the pile, you find the oldest faults.

The data structure to manage the relay trips, addresses (3700h-3718h), implies an additional complexity that is to bring all the faults to be able to find the newest one.
So far the problem. Now, I am getting in touch to see if there is a more recent failure rate, such that, for example, starting from the base address 3700h + index, I can retrieve the last shot in a single question..

_____________________________________________________________
Product Line
MiCOM P12x, P12y

_____________________________________________________________
Environment
Normal.

_____________________________________________________________
Solution
Latest non-acknowledged fault record can be retrieved from Address 3E00h. Each new record have to be either retrieved or manually acknowledged to keep the register abreast with latest record.

Modbus address for oldest fault record

Modbus address 3Eh description Modbus format F9 description


_____________________________________________________________

*Warning:  Installation, maintenance, up-gradation, down-gradation of MiCOM device should only be performed by qualified, competent personnel that have appropriate training and experience. Failure to follow the instructions / warnings in the Installation / Operation Guide can result in unwanted disruption to the power system, permanent damage to the device, severe injury or death.*

施耐德電機Taiwan

附件
Complaint.png [79.54 KB]
探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings