Ecostruxure Automation Expert [21.1]: How to resolve logging issues for newly added user in Ecostruxure Automation Expert.

This document explains on How to resolve logging issues for newly added users in Ecostruxure Automation Expert.

While creating a Project in Ecostruxure Automation Expert, System asks for creation of at least one user mandatorily for security purposes.

Later in Topology, the user will Configure the security of the device and Trust it. Thus the device can be connected and deployed using the User credentials created which is normal procedure. Users can see the security status as below once it's configured.

p1

Issue: Issue comes when the User creates a new "user" in the project and tries to connect with the Controller using the newly created credentials. The logging with new credentials will fail.

Resolution: When User is creating a new "User in project, the User credentials will be automatically outdated at Topology, as shown in below picture. So you need to go to topology and right click on the device and click on Configure security. This will update the new users & credentials to the Controller. After this, user can log in with New user credentials to the controller.

p2

This document is applicable from Ecostruxure Automation Expert 21.1 version onwards.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings