Micrologic X with Self Diagnostic trip code 0x6407 and ENCT disconnected alarm code 0x1403
Issue: Self Diagnostic trip and External Neutral CT disconnected alarm
Product Line: Circuit Breakers
Environment: Masterpact MTZ, Micrologic X, Xi control unit

Resolution:
Self-diagnostic trip without trip code
Error code HMI Error code
OR
Self-diagnostic trip with 0x6407 code
Error CodesTrip History

AND
Go into alarm history and see if you also have a ENCT disconnected alarm.
Alarm history

Do not replace the control unit.
  1. There may be an intermittent connection in the eNCT metering chain. Check continuity and stable resistance values in the eNCT metering chain (T1-T2 jumper,  wiggle the wago and  wago wires, eNCT harness, eNCT)
  2. If the breaker does not have the eNCT installed. The T1-T2 Jumper may be missing.
  3. The eNCT wiring harness may be missing.
  4. The breaker may be racked out of the cradle and therefore is disconnected from the eNCT

Check the eNCT declaration in the control unit display
If there is no eNCT installed, the eNCT declaration should be set to "NO"
If there is an eNCT installed, normally the eNCT declaration is set to "YES".  The declaration can be set to "NO" to disable the self diagnostic on the eNCT circuit.  However, it also turns off the displayed neutral current and neutral protection, but the neutral measurement will still be included in the ground fault calculation and GF will still operate normally.

Control Unit navigation path to ENCT declaration:
Home button
Configuration
Measures
System type

System Type

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings