UPS firmware file transfer using Network Management Card web interface fails

Article available in these languages:

  • 法文

Issue: UPS firmware file transfer using the Network Management Card (NMC) web interface fails

Product Line:
  • Smart-UPS models with a SmartSlot or embedded NMC.
Environment:
  • UPS systems with Network Management Card 2 (AP9630, AP9630CH, AP9631, AP9631CH, or embedded NMC2) firmware v.6.8.0 or higher:
  • UPS systems with Network Management Card 3 (AP9640, AP9641, AP9643, or embedded NMC3)

Cause: When performing the UPS firmware update using the NMC web interface, while connected to the web interface over WI-FI, a different network, or VPN, a file transfer timeout may occur if an HTTPS connection is used.

Resolution:

Option 1 (RECOMMENDED): The transfer timeout will not occur if the firmware transfer is performed over an SCP connection. Follow the steps outlined in FAQ000242942 to update the UPS firmware remotely using SCP and command line interface.

Option 2: The transfer timeout will not occur if the firmware transfer is performed over an HTTP connection, but this is not recommended due to lack of encryption.

Step 1: In the web interface of the NMC, enable HTTP in "Configuration", "Network", "Web", "Access", and select "Apply":
enableHTTP


Step 2: Reboot the NMC. This will not affect the load connected to the UPS.
Enable "Reboot Management Interface" in Navigate to "Control", "Network", "Reset/Reboot", and select "Apply":
rebootNMC

Confirm the reboot:
rebootNMC2

You will be logged off. Select Log On:
loginNMC


Step 3: Click the URL and manually change https to http. Press Enter.
URLedit


Step 4: Log in using your user name and password. Follow the steps outlined in FA170679 to update the firmware of your UPS.


Step 5: Once the firmware update has completed, HTTP access can now be disabled. Deselect HTTP in "Configuration", "Network", "Web", "Access", and select "Apply".

disableHTTP

Step 6: Refer to Step 2 to reboot the NMC.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings