SchneiderElectric_KBA_Basic_Meter_PM55xx Russian Language files issue

SchneiderElectric_KBA_Basic_Meter_PM55xx Russian Language files issue

Problem statement :

Pm5560 Meter set to Russian language, the Panel data is not visible and some of data labels are not visible in different screen navigations.
Russian Language issue

Causes identified :

  • This data label missing or data is missing in PM55xx when the Meter is set to the Russian language.
  • This is due to an issue with the Russian language file used within PM55xx.
  • This issue is noticed with Pm55xx with firmware versions below 4.1.3


Solution :

  • This issue is fixed in Firmware version 4.1.3 onwards. So the meter needs to be upgraded to this Firmware version.

施耐德電機Taiwan

附件
SchneiderElectric_KBA_Basic_Meter_PM55xx_Russian_language_Issue.pdf [347.55 KB]